OMEGA-X ADDRESSABLE FIRE ALARM CONTROL PANEL
- UL 864 9th Edition listed.
- Multi-Loop 2 Analog Addressable Loops Field upgradable to 4.
- 126 primary points per loop.
- Powerful, network wide cause and effects (500 total) .
- Fully user programmable by point or zone.
- 800 points per panel when using devices with sub-points.
- Up to 3048 m wiring length on SLC loop.
- 64 Panels on a network.
- Supervised Powered Outputs – 3.
- 4 Programmable notification appliance circuits.
- Power per NAC: 1.6 A maximum.
- Programmable outputs on SLC loop.
OMEGA R ADDRESSABLE REPEATER PANEL
- Available in Red.
- Up to 15 annunciators can be connected to each SHIELD Omega fire control panel.
- Large liquid crystal display (240×64 pixels).
- High brightness LED indications.
- Internal sounder.
- Replicates all panel controls.
- Simple, two-wire serial connection.
- Small, style enclosure.
- Removable electronics for easy installation.
- 24 V DC powered.
- Low power consumption.
- Multi language options.
- Connection supervised by SHIELD Omega fire control panel.
GRAPHICAL USER INTERFACE FOR FIRE DETECTION EQUIPMENT
- Choice of text, graphic, event list display when an event occurs.
- Versatile event analysis.
- Total history archive.
- Easy to programme.
- Secure system.
- Cost effective compared to other systems.
- Simple to use.
- Unlimited map linking & zoom facility.
- Support for 100’s of graphics.
- Display and control for multiple panels.
- Event history explore and export facility to text or HTML documents.
H3 tag with specific typography
- SPECIFICATION
- DETECTOR TYPE Photoelectric
- WORKING VOLTAGE 17 – 28 V DC
- MODULATION VOLTAGE (V PEAK TO PEAK) 5 – 9 V
- MAXIMUM ALARM CURRENT LED ON 4.5 mA
- SURGE CURRENT 1.0 mA
- SUPERVISORY CURRENT 340 μA
- TEST METHOD Home Safeguard, Gemini 501
- STORAGE TEMPERATURE RANGE -30°C to +80°C
- OPERATING TEMPERATURE RANGE -20°C to +60°C
- DIMENSIONS (DIAMETER X HEIGHT) 100 mm x 42 mm
- WEIGHT 105 g
FIXED TEMP/RATE OF RISE HEAT SENSOR
- SPECIFICATION
- DETECTOR TYPE Heat
- WORKING VOLTAGE 17 – 28 V DC
- MODULATION VOLTAGE (V PEAK TO PEAK) 5 – 9 V
- MAXIMUM ALARM CURRENT LED ON 2.5 mA
- SURGE CURRENT 1.0 mA
- SUPERVISORY CURRENT 250 μA
- HEAT ELEMENT RATING 135°F (57°C)
- TEST METHOD Hair Dryer
- DIMENSIONS (DIAMETER X HEIGHT) 100 mm x 42 mm
- WEIGHT 105 g
MULTI-CRITERIA SENSOR – SMOKE, HEAT
- SPECIFICATION
- DETECTOR TYPE Photoelectric Smoke Sensor and Thermistor
- WORKING VOLTAGE 17 – 28 V DC
- MODULATION VOLTAGE (V PEAK TO PEAK) 5 – 9 V
- MAXIMUM ALARM CURRENT LED ON 3.5 mA
- SURGE CURRENT 0 mA
- SUPERVISORY CURRENT 500 μA
- TEST METHOD Home Safeguard, Gemini 501
- DIMENSIONS (DIAMETER X HEIGHT) 100 mm x 50 mm
- WEIGHT 105 g
STANDARD MOUNTING BASE
SHIELD Mounting Base which is a low insertion force base with stainless steel contacts for the detector terminals. XPERT Cards are supplied with all bases.
Specifications
■ XPERT addressing.
■ One way FIT
■ Locking feature to prevent unauthorized removal.
RELAY OUTPUT MODULE
- SPECIFICATION
- TYPE Relay Output Module
- STYLE Fascia Plate With Wiring Terminals
- TEMPERATURE RANGE 0°C to 49°C
- WIRING SIZE 24 AWG – 14 AWG
- SIGNAL LINE CIRCUIT (SLC) Supervised Power Limited
- WORKING VOLTAGE 17 – 28 V DC
- MODULATION VOLTAGE 5 – 9 V DC (peak to peak)
- Supervised, Dry Contact
- 24 V DC, 2 A; 30 V DC, 0.5 A
- DIMENSIONS (L X W X D) 114 mm x 114 mm x 25 mm
SWITCH MONITOR MODULE
- SPECIFICATION
- TYPE Switch Monitor Module
- STYLE Fascia Plate With Wiring Terminals
- TEMPERATURE RANGE 0°C to 49°C
- WIRING SIZE 24 AWG – 14 AWG
- SIGNAL LINE CIRCUIT (SLC) Supervised Power Limited
- WORKING VOLTAGE 17 – 28 V DC
- MODULATION VOLTAGE 5 – 9 V DC (peak to peak)
- OPERATING CURRENT Supervisory Current 1.1 mA
- Surge Current 2.5 mA
- Maximum Alarm Current 5 mA (LED on
- FUNCTIONAL STATES Analog Level (normal) 16
- Analog Level (alarm)) 64
- Analog Level (trouble) 4
- DIMENSIONS (L X W X D) 114 mm x 114 mm x 25 mm
DUAL ACTION PULL STATION
The Addressable Manual Pull Station is dual action and features translucent plastic at the center, allowing visibility of an internal LED that indicates alarm condition and polling status. The unit is addressable using a DIP switch protected within the pull station. The Manual Pull Station may be flush mounted on a single gang work box or use an optional back cover..
- SPECIFICATION
- OPERATING VOLTAGE 17 – 28 V DC
- 20 – 28 V DC (UL Listed)
- CURRENT CONSUMPTION AT 24 V Normal Standby 200μA
- Operated 3.6 mA + Quiescent
- IP RATING 25
- DIMENSIONS (W X H X D) MM Pull Station 108 x 140x 28
- Back Box 108 x 140x 45
- WEIGHT Pull Station 200 g
- Back Box 326 g
OPEN AREA SOUNDER
SHIELD Open-Area Sounder has been designed for use in open areas and can be connected to any UL or SHIELD system.
- SPECIFICATION
- OPERATING VOLTAGE 17 – 28 V DC
- MAXIMUM LOW CURRENT AT 24 V Normal Standby < 310μA
- Operated 28V Highest Audibility 5.4 mA
- Operated Switch On Surge < 6 mA for IS
- IP RATING 65
OPEN AREA SOUNDER BEACON
SHIELD UL Open-Area Sounder Beacon makes full use of the protocol and has been designed for use in indoor, outdoor and open-areas. When the fire system is being commissioned, a Magnetic Wand can be used to adjust and test each sounder locally.
- SPECIFICATION
- OPERATING VOLTAGE 17 – 28 V DC
- SOUNDER OPERATING Variable
- MAXIMUM LOW CURRENT AT 24 V Normal Standby < 750μA
- Operated 28V Highest Audibility 5.4 mA
- Operated Switch On Surge < 6 mA for IS
- IP RATING 65
ALPHA 1000 REFLECTIVE BEAM DETECTOR
- Easy set up and alignment.
- Single compact housing.
- Calibrated obscuration test filter included.
- Microprocessor controlled.
- Alarm latching or auto reset.
- Automatic gain control.
- 12 V DC or 24 V DC operation.
- Separate alarm and trouble contacts.
- Remote Test Station available.
ALPHA 3000 END TO END BEAM DETECTOR
- Separate Transmitter and Receiver Heads.
- Range 5 m to 120 m, configurable per set of Detectors.
- Lateral Spacing per NFPA 72 is 18 m.
- Integral Laser Alignment in Receiver.
- 2-wire Interface between Controller and Receiver.
- Single and Twin Channel capability.
- Separate Fire and Fault Relays per Detector.
- Low Level Controller with LCD display.
- Programmable Sensitivity and Fire Threshold.
- Automatic Gain Control (AGC) for drift compensation.
- Built-in electronic UL/ULC obscuration-acceptance fire test.
- Knockouts for ease of installation and wiring.
- Optional Transmitter powering from Controller.
ALPHA 5000 AUTO ALIGN BEAM DETECTOR
- Up to 2 Detector Heads reporting to One Ground Level Controller
- Built in Laser assisted prism mounting
- Auto-Alignment 2 to 4 minutes per head
- AutOptimise: Auto-Correction due to building shift
- Built-in electronic UL/ULC obscuration-acceptance fire test
- Contamination compensation
- Separate Trouble and Alarm relays for each of the 2 channels
- Password protected settings
- Programmable alarm thresholds: 10% – 60% in 1% increments
- Programmable Fault and Alarm delay: 2-30 Seconds
ISOLATOR MODULE
- PRIMARY INPUT POWER 14 to 36 V DC
- STANDBY CURRENT
- (DEPENDING ON NUMBER OF DETECTOR HEADS) Low Current : 5 mA to 8.5 mA @ 24 V DC
- High Current : 37 mA @ 24 V DC
- ALARM CURRENT 5 mA to 8.5 mA @ 24 V DC Depending On Number Of Detector Heads Used
- RELAY CONTACTS 1 A @ 30 V DC Resistive
- RESET TIME 5 Seconds Maximum
- START UP TIME 45 Seconds
- OPTICAL WAVELENGTH 850 nm
- TEMPERATURE RATING UL LISTED 0°C to 38°C
- IP RATING IP54
- DIMENSION (W X H X L) & WEIGHT
- HEAD 134 mm x 134 mm x 131 mm, 1470 g
- CONTROLLER 202 mm x 87 mm x 230 mm, 1470 g
- PRISM 100 mm x 9.5 mm x 105 mm
FIRE PROOF CABLE (FPLR TYPE)
Shield Fire Proof Cable is available in a variety of multiple core combinations all with CPC (circuit protection conductor). 500m reels and other special lengths are available.
- Supplied on robust plastic reels.
- Installer safe and easy handling.
- Better reeling and damage resistant.
- Weather and moisture resistant.
DIGITAL LHD CABLE
Shield Digital Linear Heat Detection Cable uses xed temperature detection technology to provide an easy method for sensing changes in temperature levels. The cable can oer alternative overheat protection in a vast range of applications and environments, from tunnels, cable trays, warehousing to sensing changes in temperature within escalators and other applications where many risks
of re are hidden from view.
The digital linear hear detecting cable can be directly connected to a single zone of a conventional fire alarm control panel, or, using an addressable zone/switch monitor, the digital linear heat detection cable can easily be interfaced to an addressable loop.
DIGITAL LHD CONTROL MODULE
- Advanced functionality for traditional Digital LHD systems.
- Pinpoints exact location of an incident and responds immediately.
- Simultaneous monitoring of up to two zones.
- Power indicator, fault and alarm lights for each zone.
- Volt-free outputs for fault and alarm, corresponding to each zone.
- Can be connected to an industrial process control system using the two-wire RS485 Modbus RTU output.
- Built-in sounder for audible annunciation.
- Interlock/Coincidence detection eliminates the possibility of false alarms by requiring both LHD cables to trigger before transmitting an alarm.