A Electric Fire pump, with UL Control Panel, and necessary accessories as per specification and conform to NFPA 20 Latest standard & and entire system shall be UL Listed. Pump Selection Criteria: Pumps shall furnish not less than 150 percent of rated capacity at not less than 65 percent of the total rated head. The shutoff head shall not exceed 140 percent of rated head of the pump. The vendor shall provide the Pump Curve indicating the specified performance requirements.  Provide NPSH required in feet of W.C