Diesel Engine driven Fire pump with the pump driver assemblies, UL Listed Fire Pump Control Panel, UL Listed Diesel tank with fuel piping system and fuel piping, Fuel level gauge, Pressure relief valve, dual lead acid maintenance free batteries with redundancy; Governor to maintain rated pump speed, Governor cables; Engine Exhaust Pipe with necessary flanges, fittings etc. as per specification and NFPA 20 latest standard and entire system shall be UL Listed. Pump Selection Criteria: Pumps shall furnish not less than 150 percent of rated capacity at not less than 65 percent of total rated head. The shutoff head shall not exceed 140 percent of rated head of pump. The vendor shall provide the Pump Curve indicating the specified performance requirements. Provide NPSH required in feet of W.C