UPRIGHT, PENDENT & RECESSED PENDENT Sprinkle

A fire sprinkler or sprinkler head is a part of a fire sprinkler system that releases water when the effects of a fire are detected, such as when a predetermined temperature is reached.

K-factor is used to compute the discharge rate from fire sprinkler heads. It is computed in imperial units for the United States by multiplying the flow in gallons per minute (GPM) by the pressure in PSI. A sprinkler with an imperial K factor of 5.6 produces a flow rate of 15.0 US GPM and a pressure drop of 7.2 psi. Alternatively, for a given flow rate through the sprinkler, the pressure loss can be estimated using the K value.

The SHIELD Sprinklers, SD1010, SD1015, SD1030, SD1032 (Glass Bulb Type), Standard Orifice, Upright, Pendent, and Recessed Pendent types, use cutting-edge, heat-responsive, frangible glass bulb design (standard or quick response) for quick, precise operation.

Description

SPRINKLER IDENTIFICATION NUMBER Standard SD1015, SD1010 (bulb 5mm), Quick Response SD1030, SD1032 (bulb 3mm)
STYLE Upright Sprinkler SD1015, SD1032, Pendent & Recessed Pendent SD1010, SD1030
FINISH Natural/Chrome
K FACTOR 5.6gpm/psi½. (80lpm/bar½)
RESPONSE TIME INDEX (RTI) Standard 90 (m.s)½, Quick Response 33 (m.s)½
NOMINAL THREAD SIZE ½”NPT(15mm)
ORIFICE SIZE 13mm
MAX. WORKING PRESSURE 175PSI(1200kPa)
FACTORY HYDROSTATIC TEST 100%@500PSI(3450 kPa)
MIN. OPERATION PRESSURE 7 PSI(48 kPa)