Description
Features:
Master Controller (top) bay:
• 32-Bit Master Controller with color-coded operator interface including
raised switches for high confidence feedback
• Dual configuration program CPU, convenient service port access, and
capacity for up to 3000 addressable points
• CPU assembly includes 2 GB dedicated compact flash memory for onsite system programming and information storage
• ES Power Supply (ES-PS) and charger with onboard alarm relay,
programmable auxiliary power output and provisions for one 4 in.
x 10 in. or two 4 in. x 5 in. compatible option cards such as IDNet2
addressable device interface, Conventional NAC or Addressable IDNAC
SLC modules; refer to 579-1288 installation instructions for additional
details
• Available with InfoAlarm Command Center expanded content user
interface
• Upgrade kits are available for existing control panels
Network compatibility:
Compatible with Simplex ES Net or 4120 Fire Alarm Networks
Standard addressable interfaces include:
• 250 point addressable IDNet 2 SLC channel with electrically isolated
dual short circuit isolating loops that supports TrueAlarm analog
sensors and IDNet communications monitoring and control devices
• Remote annunciator module support through RUI+ (remote unit
interface) communications port
Optional modules include:
• Building Network Interface Module (BNIC) for Ethernet connectivity
options
• Electrically isolated output IDNet 2 (two loop) and IDNet 2+2 (four loop)
modules with short circuit isolation output loops allowing use with
either shielded or unshielded, twisted or untwisted single pair wiring
• Fire Alarm Network Interfaces, DACTs, city connections, and up to five
RS-232 ports for printers and terminals
• IP communicator compatibility. Use IP Communicator Cards (IPC) for
central station reporting, refer to data sheet S2080-0090
• MAPNET II addressable device modules and MAPNET II quad isolator
modules
• IDNAC signalling line circuits (SLCs) for addressable appliance control
• Alarm relays, auxiliary relays, additional power supplies, IDC modules,
NAC expansion modules
• Service modems, VESDA Air Aspiration Systems interface, ASHRAE
BACnet Interface, TCP/IP Bridges
• LED/switch modules and panel mount printers
• Emergency communications systems (ECS) equipment; 8 channel
digital audio or 2 channel analog audio
• 8-point zone/relay module, each point is selectable as an IDC input or
relay output. Class A IDCs require two points (one out and one return).
Relays rated for 2 A @ 30 VDC (resistive) and configurable as either
normally open or normally closed.
• Compatible with Simplex remotely located 4009 IDNet NAC Extenders,
up to ten per IDNet SLC
Listings information
• UL 864, Fire Detection and Control (UOJZ), Smoke Control Service
(UUKL), Releasing Device Service (SYZV), Emergency Communication
and Relocation Equipment (UOQY)
• UL 1076, Proprietary Alarm Units – Burglar (APOU)
• UL 2017, Process Management Equipment (QVAX), Emergency Alarm
System Control Units (FSZI)
• UL 1730, Smoke Detector Monitor (UULH)
• UL 2572, Mass Notification Systems (PGWM)
• CAN/ULC-S527 Control Units for Fire Alarm Systems (UOJZ7), Releasing
Device Service (SYZV7)
• CAN/ULC-S559 Central Station Fire Alarm System Units (DAYR7)
• ULC/ORD-C1076 Proprietary Burglar Alarm Units and Systems (APOU7)
• ULC/ORD-C100 Smoke Control System Equipment (UUKL7)
Software Feature Summary
CPU provides dual configuration programs
• Two programs allow for optimal system protection and commissioning
efficiency with one active program and one reserve
• Downtime is reduced because the system stays running during
download
PC based programmer features
• Convenient front panel accessed Ethernet port for quick and easy
download of site-specific programming
• Modifications can be uploaded as well as downloaded for greater
service flexibility
• Firmware enhancements are made through software downloads to the
on-board flash memory
Operator interface features
• TrueAlarm individual analog sensing with front panel information and
selection access
• “Dirty” TrueAlarm sensor maintenance alerts, service and status
reports including “almost dirty”
• TrueAlarm magnet test indication appears as distinct “test abnormal”
message on display when in test mode
• TrueAlarm sensor peak value performance report
• Install Mode allows grouping of multiple troubles for uninstalled
modules and devices into a single trouble condition, typical with future
phased expansion; with future equipment and devices grouped into
a single trouble, operators can more clearly identify events from the
commissioned and occupied areas
• Module level ground fault searching assists installation and service by
locating and isolating modules with grounded wiring
• Recurring Trouble Filtering allows the panel to recognize, process,
and log recurring intermittent troubles, such as external wiring ground
faults, but only sends a single outbound system trouble to avoid
nuisance communications
• WALKTEST silent or audible system test performs an automatic selfresetting test cycle